Features:
• Autoranging ground resistance measurements from 0.03 to 1500 with 0.02 resolution
• True RMS AC Leakage current range of 0.2mA to 30.00A
• Programmable datalogging with 116 data points
• Programmable Hi/Lo alarm
• 0.9″ (23mm) Jaw size for large ground rods
• Simplifies ground resistance measurements on multiple point ground systems
• Auto power off
• Verification resistors confirm accuracy of meter
• Automatic Self Calibration when powered on
• 9999 Count LCD display with Data Hold
• Electrical Noise Detection feature prevents inaccurate readings
• Data hold
• Complete with 9V battery, Resistance check plate, and durable metal storage case
Specifications | Range | Resolution | Accuracy (%rdg) |
Ground Resistance | 0.025 to 0.25 | 0.002 | ±(1.5% + 0.05 ) |
0.250 to 1.000 | 0.02 | ±(1.5% + 0.05 ) | |
1.001 to 9.999 | 0.02 | ±(1.5% + 0.1 ) | |
10.00 to 50.00 | 0.04 | ±(1.5% + 0.1 ) | |
50.01 to 99.99 | 0.04 | ±(1.5% + 0.5 ) | |
100.0 to 200.0 | 0.4 | ±(1.5% + 0.5 ) | |
200.1 to 400.0 | 2 | ±(5.0% + 5 ) | |
400.0 to 600.0 | 5 | ±(10% + 10 ) | |
600.1 to 1500 | 20 | ±(20% ) | |
AC Leakage Current (Trms) | 0.300 to 1.000mA | 0.001mA | ±(2.0% + 0.05mA ) |
1.00 to 10.00mA | 0.001mA | ±(2.0% + 0.03mA) | |
10.0 to 100.0mA | 0.1mA | ±(2.0% + 0.3mA ) | |
100 to 1000mA | 0.1mA | ±(2.0% + 0.3mA ) | |
0.20 to 4.00A | 0.01A | ±(2.0% + 0.03A ) | |
4.00 to 30.00A | 0.01A | ±(2.0% + 0.03A ) | |
Resistance Test Frequency | 1.667kHz | ||
Diemnsions | 10.2 x 4.4 x 1.9″ (258 x 110 x 47mm) | ||
Weight | 24.7oz (700g) |